Rockwell Automation 20A PowerFlex 70 Adjustable Frequency AC Drive User Manual
Page 51
Rockwell Automation Publication 20A-IN009D-EN-P - June 2013
51
PowerFlex 70 Adjustable Frequency AC Drive
Table 22 - Abbreviated Alarm Table
Alarm
No.
Ty
pe
(1
)
(1) See PowerFlex 70 User Manual, publica
Description
Dig In ConflictA
17
2
Digital input functions are in conflict. Combinations marked with an “X” will
cause an alarm.
Dig In ConflictB
18
2
A digital Start input has been configured without a Stop input or other
functions are in conflict. Combinations that conflict are marked with an “X” and
will cause an alarm.
Dig In ConflictC
19
2
More than one physical input has been configured to the same input function.
Multiple configurations are not allowed for the following input functions:
• Forward/Reverse, Run Reverse, Bus Regulation Mode B
• Speed Select 1, Jog Forward, Acc2 / Dec2
• Speed Select 2, Jog Reverse, Accel 2
• Speed Select 3, Run, Decel 2
• Run Forward, Stop Mode B
TB Man Ref Cflct
30
Occurs when:
“Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363
and
[TB Man Ref Sel], parameter 96 has been reprogrammed.
No other use for the selected analog input can be programmed.
Example: If [TB Man Ref Sel] is reprogrammed to “Analog In 2,” all of the factory
default uses for “Analog In 2” must be reprogrammed (such as parameters 90,
117, 128 and 179). Refer to the Auto/Manual Examples section of the PowerFlex
70 User Manual, publicatio
.
To correct:
Verify/reprogram the parameters that reference an analog input
or
Reprogram [Digital In3] to another function or “Unused.”
Acc2/Dec2 Accel 2
Decel 2
Jog
Jog Fwd
Jog Rev
Fwd/Rev
Acc2 / Dec2
X
X
Accel 2
X
Decel 2
X
Jog
X
X
Jog Fwd
X
X
Jog Rev
X
X
Fwd / Rev
X
X
Start Stop–CF Run Run Fwd Run Rev Jog Jog Fwd Jog Rev Fwd/
Rev
Start
X
X
X
X
X
Stop–CF
Run
X
X
X
X
X
Run Fwd X
X
X
X
Run Rev
X
X
X
X
Jog
X
X
Jog Fwd
X
X
Jog Rev
X
X
Fwd / Rev
X
X
E C