Rockwell Automation Publication 20A-IN009D-EN-P - June 2013

53

PowerFlex 70 Adjustable Frequency AC Drive

Table 25 - Drive Does Not Respond to Changes in Speed Command

Table 26 - Motor and/or Drive does Not Accelerate to Commanded Speed

Table 27 - Motor Operation is Unstable

Manually Clearing Faults

Cause

Indication

Corrective Action

No value is coming from the source
of the command.

LCD HIM
Status Line
indicates “At
Speed” and
output is 0
Hz.

1. If the source is an analog input, check wiring and use a

meter to check for presence of signal.

2. Check [Commanded Freq] for correct source.

Incorrect reference source has been
programmed.

None

1. Check [Speed Ref Source] for the source of the speed

reference.

2. Reprogram [Speed Ref A Sel] for correct source.

Incorrect reference source is being
selected via remote device or digital
inputs.

None

1. Check [Drive Status 1], bits 12 and 13 for unexpected

source selections.

2. Check [Dig In Status] to see if inputs are selecting an

alternate source.

3. Reprogram digital inputs to correct “Speed Sel x” option.

Cause

Indication

Corrective Action

Acceleration time is excessive.

None

Reprogram [Accel Time x].

Excess load or short acceleration
times force the drive into current
limit, slowing or stopping
acceleration.

None

Check [Drive Status 2], bit 10 to see if the drive is in Current
Limit.
Remove excess load or reprogram [Accel Time x].

Speed command source or value is
not as expected.

None

Check for the proper Speed Command by using

Table 25 on

page 53

.

Programming is preventing the
drive output from exceeding
limiting values.

None

Check [Maximum Speed] and [Maximum Freq] to assure that
speed is not limited by programming.

Cause

Indication

Corrective Action

Motor data was incorrectly entered
or Autotune was not performed.

None

1. Correctly enter motor nameplate data.
2. Perform “Static” or “Rotate” Autotune procedure.

Step

Key(s)

1. Press Esc to acknowledge the fault.

The fault information is removed so that you can use the Human Interface Module (HIM).

2. Address the condition that caused the fault.

The cause must be corrected before the fault can be cleared.

3. After corrective action has been taken, clear the fault by one of these methods:

• Press Stop.
• Cycle drive power.
• Set parameter 240 [Fault Clear] to “1”.
• “Clear Faults” on the Human Interface Module (HIM) Diagnostic menu.

Esc