PowerFlex 70 Adjustable Frequency AC Drive

Jumper Settings and Locations

Fram

e

Vo

lt

ag

e

Co

de

Factory Default Jumper Settings

Power Source Type

MOV/Input Filter Caps

DC Bus Common Mode
Caps

A

B
C
D
E

JP2/JP3
Installed

Not applicable

Solid ground
Insert jumper at the “JP2/JP3” location.

Non-solid ground
Remove the jumper at “JP2/JP3.”

B

B
D
E

JP2/JP3
Installed

JP5/JP6
Not installed

Important: The internal EMC filter (input filter) is a
factory-installed option on frame B drives. If the option
is installed, the drive cannot be used on a non-solid
ground power source.
To verify: an extra “R, S, T” terminal block is present if
the option is installed (as shown). Additionally, the 13th
character of the nameplate catalog number is “A”
(see

page 31

).

Solid ground
Install jumpers at both locations (JP2/JP3 and JP5/JP6).

Non-solid ground
Remove the jumper at “JP2/JP3.” Verify that the jumper
at “JP5/JP6” is also removed. In addition, verify that the
input filter option is not installed.

C

JP2/JP3
Installed

JP5/JP6
Installed

JP3

JP2

MOV

JP3

JP2

JP5

JP6

MOV

CM Cap

L1

R

L2

S

L3

T

BR1
+DC

L1

R

L2

S

L3

T

Input Filter

Option

JP6 JP5

JP3

JP2

MOV

CM Cap

L1

R

L2

S

L3

T

BR1
+DC

L1

R

L2

S

L3

T

Input Filter

Option

or