Table 4 - Wiring Specifications

AC Supply Source Considerations

PowerFlex 70 drives are suitable for use on a circuit capable of delivering up to a
maximum of 200,000 rms symmetrical amperes, and a maximum of 600V.

If the drive has a system ground fault monitor (residual current device), use
Type B (adjustable) devices to avoid nuisance tripping.

Unbalanced, Ungrounded, High Resistance or B-phase Grounded Distribution Systems

Install an isolation transformer on an ungrounded distribution system where the
line-to-ground voltages on any phase could exceed 125% of the nominal line-to-
line voltage. See Wiring and Grounding Guidelines for PWM AC Drives,
publication

DRIVES-IN001

, for more information on impedance grounded and

ungrounded systems.

Type

Wire Types

Description

Min Insulation
Rating

Power

(1)(2)

(1) Control and signal wires must be separated from power wires by at least 0.3 m (1 ft).
(2) We recommend the use of shielded wire for AC input power (even if it is not necessary).

Standard

600V, 90 °C (194 °F)
XHHW2/RHW-2
Anixter
B209500-B209507,
Belden 29501-29507,
(or equivalent)

Four tinned copper conductors
with XLPE insulation.
Copper braid/aluminum foil
combination shield and tinned
copper drain wire.
PVC jacket.

Signal

(1) (3)

(4)

(3) If the wires are short and contained within a cabinet that has no sensitive circuits, we recommend the use of shielded wire (even if it

is not necessary).

(4) I/O terminals labeled “(–)” or “Common” are not referenced to earth ground and are designed to greatly reduce common mode

interference. Grounding these terminals can cause signal noise.

Standard
analog I/O

Belden 8760/9460

(or equivalent)

0.750 mm

2

(18 AWG), twisted

pair, 100% shield with drain.

300V,
75…90 °C
(167…194 °F)

Belden 8770
(or equivalent)

0.750 mm

2

(18 AWG),

three-conductor,
shielded for remote pot.

Digital I/O

(1) (3) (4)

Shielded

Multi-conductor
shielded cable such as
Belden 8770
(or equivalent)

0.750 mm

2

(18 AWG),

three-conductor,
shielded.

300V,
60 °C (140 °F)

ATTENTION: To guard against personal injury and/or equipment damage
caused by improper fusing or circuit breaker selection, use the recommended
line fuses/circuit breakers specified in

Drive, Fuse, and Circuit Breaker Ratings

on page 25

.