Common Symptoms and Corrective Actions

Table 23 - Drive Does Not Start From Start or Run Inputs Wired to the Terminal Block

Table 24 - Drive Does Not Start From the Human Interface Module (HIM)

Cause

Indication

Corrective Action

Drive is Faulted

Flashing red status
light

Clear fault.
Press Stop
Cycle power
Set [Fault Clear] to 1
“Clear Faults” on the HIM Diagnostic

menu

Incorrect input wiring.
See page

35

for wiring examples.

2 wire control requires Run, Run Forward,

Run Reverse or Jog input.

3 wire control requires Start and Stop inputs
Jumper from terminal 7 to 8 is required.

Flashing green
status light

Wire inputs correctly and/or install jumper.

Incorrect digital input programming.
Mutually exclusive choices have been made

(i.e., Jog and Jog Forward).

2-wire and 3-wire programming can be

conflicting.

Exclusive functions (for example, direction

control) can have multiple inputs
configured.

Stop is factory default and is not wired.

None

Program [Digital Inx Sel] for correct inputs.
Start or Run programming can be missing.

Flashing yellow
status light and
“DigIn CflctB”
indication on LCD
HIM.
[Drive Status 2]
shows type 2
alarm(s).

Program [Digital Inx Sel] to resolve conflicts.
Remove multiple selections for the same
function.
Install stop button to apply a signal at stop
terminal.

Safe Torque Off Option Installed
Hardware Enable Input “Digital In 6” not

present.

Flashing yellow
status light and
“Not Enable”
indication on LCD
HIM.

Verify correct wiring to “Digital In 6.”
Check for presence of signal.

Safe Torque Off Option inputs not present.

Flashing yellow
status light and
“Safe-Off”
indication on LCD
HIM.

Wire inputs correctly on Safe Off option
terminals 1 through 4.
Refer to the DriveGuard Safe Torque Off
Option User Manual, publication

PFLEX-

UM003

for additional information

Cause

Indication

Corrective Action

Drive is programmed for 2-wire control.
Human Interface Module (HIM) Start
button is disabled for 2-wire control.

None

If 2-wire control is required, no action is necessary.
If 3-wire control is required, program [Digital Inx Sel]
for correct inputs.