Common symptoms and corrective actions – Rockwell Automation 20A PowerFlex 70 Adjustable Frequency AC Drive User Manual
Page 52
![background image](/manuals/577203/52/background.png)
52
Rockwell Automation Publication 20A-IN009D-EN-P - June 2013
PowerFlex 70 Adjustable Frequency AC Drive
Common Symptoms and Corrective Actions
Table 23 - Drive Does Not Start From Start or Run Inputs Wired to the Terminal Block
Table 24 - Drive Does Not Start From the Human Interface Module (HIM)
Cause
Indication
Corrective Action
Drive is Faulted
Flashing red status
light
Clear fault.
• Press Stop
• Cycle power
• Set [Fault Clear] to 1
• “Clear Faults” on the HIM Diagnostic
menu
Incorrect input wiring.
See page
for wiring examples.
• 2 wire control requires Run, Run Forward,
Run Reverse or Jog input.
• 3 wire control requires Start and Stop inputs
• Jumper from terminal 7 to 8 is required.
Flashing green
status light
Wire inputs correctly and/or install jumper.
Incorrect digital input programming.
• Mutually exclusive choices have been made
(i.e., Jog and Jog Forward).
• 2-wire and 3-wire programming can be
conflicting.
• Exclusive functions (for example, direction
control) can have multiple inputs
configured.
• Stop is factory default and is not wired.
None
Program [Digital Inx Sel] for correct inputs.
Start or Run programming can be missing.
Flashing yellow
status light and
“DigIn CflctB”
indication on LCD
HIM.
[Drive Status 2]
shows type 2
alarm(s).
Program [Digital Inx Sel] to resolve conflicts.
Remove multiple selections for the same
function.
Install stop button to apply a signal at stop
terminal.
Safe Torque Off Option Installed
• Hardware Enable Input “Digital In 6” not
present.
Flashing yellow
status light and
“Not Enable”
indication on LCD
HIM.
Verify correct wiring to “Digital In 6.”
Check for presence of signal.
Safe Torque Off Option inputs not present.
Flashing yellow
status light and
“Safe-Off”
indication on LCD
HIM.
Wire inputs correctly on Safe Off option
terminals 1 through 4.
Refer to the DriveGuard Safe Torque Off
Option User Manual, publication
Cause
Indication
Corrective Action
Drive is programmed for 2-wire control.
Human Interface Module (HIM) Start
button is disabled for 2-wire control.
None
If 2-wire control is required, no action is necessary.
If 3-wire control is required, program [Digital Inx Sel]
for correct inputs.