Clearing alarms, Alarm descriptions, Clearing alarms -6 alarm descriptions -6 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 88: Alarm descriptions on, R to, Table 4.c

4-6
Troubleshooting
Table 4.B Fault Cross Reference – by Number
Clearing Alarms
Alarms are automatically cleared when the condition that caused the alarm
is no longer present.
Alarm Descriptions
No.
(1)
(1)
Fault numbers not listed are reserved for future use.
Fault
No.
(1)
Fault
No.
(1)
Fault
2
Auxiliary Input
41
Phase UV Short
81- 85
Port 1-5 DPI Loss
3
Power Loss
42
Phase VW Short
87
IXo VoltageRange
4
UnderVoltage
43
Phase UW Short
88
Software Fault
5
OverVoltage
48
Params Defaulted
89
Software Fault
7
Motor Overload
49
Drive Powerup
93
Hardware Fault
8
Heatsink OvrTemp
51
Flt QueueCleared
100
Parameter Chksum
9
Trnsistr OvrTemp
52
Faults Cleared
101-103 UserSet Chksum
12
HW OverCurrent
55
Cntl Bd Overtemp
104
Pwr Brd Chksum1
13
Ground Fault
63
Shear Pin
105
Pwr Brd Chksum2
24
Decel Inhibit
64
Drive OverLoad
106
Incompat MCB-PB
25
OverSpeed Limit
68
Gate Kill
107
Replaced MCB-PB
29
Analog In Loss
69
DB Resistance
108
Anlg Cal Chksum
33
Auto Rstrt Tries
71- 75 Port 1-5 Adapter
120
I/O Mismatch
36
SW OverCurrent
77
IR Volts Range
121
I/O Comm Loss
38
Phase U to Grnd
78
FluxAmpsRef Rang
122
I/O Failure
39
Phase V to Grnd
79
Excessive Load
130
Hardware Fault
40
Phase W to Grnd
80
AutoTune Aborted
131
Hardware Fault
Table 4.C Alarm Descriptions and Actions
Alarm
No. Type
(1)
Description
Analog In Loss
5
➀
An analog input is configured for “Alarm” on signal loss and signal
loss has occurred.
Bipolar Conflict
20
➁
Parameter 190 [Direction Mode] is set to “Bipolar” or “Reverse Dis”
and one or more of the following digital input functions is configured:
“Fwd/Reverse,” “Run Forward,” “Run Reverse,” “Jog Forward” or
“Jog Reverse.”
Decel Inhibt
10
➀
Drive is being inhibited from decelerating.
Dig In ConflictA
17
➁
Digital input functions are in conflict. Combinations marked with a
“ ” will cause an alarm.
Acc2/Dec2
Accel 2 Decel 2 Jog
Jog
Fwd
Jog
Rev
Fwd/
Rev
Acc2 / Dec2
Accel 2
Decel 2
Jog*
Jog Fwd
Jog Rev
Fwd/Rev