Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 78

3-30
Programming and Parameters
INPUTS & OUTPUTS
Digital I
nputs
361
362
363
364
365
366
[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]
Selects the function for the digital inputs.
(1)
Speed Select Inputs.
To access Preset Speed 1, set [Speed Ref x Sel] to “Preset Speed 1.”
Type 2 Alarms - Some digital input programming may cause conflicts
that will result in a Type 2 alarm. Example: [Digital In1 Sel] set to
option 5 “Start” in 3-wire control and [Digital In2 Sel] set to option 7
“Run” in 2-wire.
Refer to
for information on resolving this type of conflict.
(2)
When [Digital Inx Sel] is set to option 2 “Clear Faults,” the Stop button
cannot be used to clear a fault condition.
(3)
Typical 3-Wire Inputs - Requires that only 3-wire functions are chosen.
Including 2-wire selections will cause a Type 2 alarm.
Default:
Default:
Default:
Default:
Default:
Default:
Options:
4
5
18
15
16
17
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15-17
18
19
20
21
22
23
24
25
26
27
28
29
30
“Stop – CF”
“Start”
“Auto/ Manual”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Not Used”
“Enable”
(6) (8)
“Clear Faults” (CF)
(2)
“Aux Fault”
“Stop – CF”
(8)
“Start”
(3) (7)
“Fwd/ Reverse”
(3)
“Run”
(4) (8)
“Run Forward”
(4)
“Run Reverse”
(4)
“Jog”
(3)
“Jog Forward”
(4)
“Jog Reverse”
(4)
“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1-3”
(1)
“Auto/ Manual”
(5)
“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
“MOP Dec”
“Excl Link”
“PI Enable”
“PI Hold”
“PI Reset”
“Pwr Loss Lvl”
“Precharge En”
100
194
380
124
(4)
Typical 2-Wire Inputs - Requires that only 2-wire functions are chosen. Including 3-wire selections will cause a Type
2 alarm. See
for conflicts.
(5)
Auto/Manual - Refer to
for details.
(6)
Opening an “Enable” input will cause the motor to coast-to-stop, ignoring any programmed Stop modes.
(7)
A “Dig In ConflictB” alarm will occur if a “Start” input is programmed without a “Stop” input.
(8)
Refer to the Sleep-Wake Mode Attention statement on
.
Fil
e
Gr
oup
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Related
3
2
1
Auto Reference Source
0
0
0
0
1
1
1
1
0
0
1
1
0
0
1
1
0
1
0
1
0
1
0
1
Reference A
Reference B
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7