Programming and Parameters
3-29
INPUTS
&
OUTPUTS
Ana
log Outputs
341
[Anlg Out Absolut]
Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog
output.
342
[Analog Out1 Sel]
Selects the source of the value that drives the analog output.
Default:
Options:
0 “Output Freq”
See Table
001
,
002
,
003
,
004
,
005
,
006
,
007
,
012
,
135
,
136
,
137
,
138
,
220
,
219
343
[Analog Out1 Hi]
Sets the analog output value when the source value is at maximum.
Default:
Min/Max:
Units:
20.000 mA, 10.000 Volts
4.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt
344
[Analog Out1 Lo]
Sets the analog output value when the source value is at minimum.
Default:
Min/Max:
Units:
0.000 mA, 0.000 Volts
4.000/20.000mA
–/+10.000V
0.000/10.000V
0.001 mA
0.001 Volt
Fil
e
Gr
oup
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Related
x x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Absolute
0 =Signed
x =Reserved
Bit #
Factory Default Bit Values
Analog Out1
Options
[Analog Out1 Lo] Value
[Analog Out1 Hi] Value
Param. 341 = Signed
Param. 341 = Absolute
0
1
2
3
4
5
6
7
8
9
10
11
12
13
“Output Freq”
“Command Freq”
“Output Amps”
“Torque Amps”
“Flux Amps”
“Output Power”
“Output Volts”
“DC Bus Volts”
“PI Reference”
“PI Feedback”
“PI Error”
“PI Output”
“%Motor OL”
“%Drive OL”
–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
0 Hz
0 Hz
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated Input Volts
200% Rated Input Volts
100%
100%
100%
100%
100%
100%