Chapter 2, Start up, Prepare for drive start-up – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 45: Before applying power to the drive, Prepare for drive start-up -1

Chapter
2
Start Up
This chapter describes how you start up the LPM15. Refer to
for a brief description of the LCD HIM (Human Interface Module).
Prepare For Drive Start-Up
Before Applying Power to the Drive
❏ 1. Confirm that all inputs are connected to the correct terminals and are
secure.
❏ 2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
❏ 3. Verify that control power voltage is correct.
The remainder of this procedure requires that a HIM be installed. If an
operator interface is not available, remote devices should be used to start
up the drive.
For information on…
See page…
!
ATTENTION: Power must be applied to the drive to perform
the following start-up procedure. Some of the voltages present
are at incoming line potential. To avoid electric shock hazard or
damage to equipment, only qualified service personnel should
perform the following procedure. Thoroughly read and
understand the procedure before beginning. If an event does not
occur while performing this procedure, Do Not Proceed.
Remove Power including user-supplied control voltages. User
supplied voltages may exist even when main AC power is not
applied to the drive. Correct the malfunction before continuing.