3-12
Programming and Parameters
SPEED
COMMAND
Disc
re
te Spee
ds
100
[Jog Speed]
Sets the output frequency when a jog command is issued.
Default:
Min/Max:
Units:
10.0 Hz
–/+[Maximum Speed]
0.1 Hz
101
102
103
104
105
106
107
[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]
Provides an internal fixed speed command value. In bipolar mode
direction is commanded by the sign of the reference.
Default:
Min/Max:
Units:
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz
–/+[Maximum Speed]
0.1 Hz
090
,
093
Speed T
rim
117
[Trim In Select]
Specifies which analog input signal is being used as a trim input.
Default:
Options:
2
“Analog In 2”
See
[Speed Ref A Sel]
090
,
093
118
[Trim Out Select]
Specifies which speed references are to be trimmed.
117
,
119
,
120
119
[Trim Hi]
Scales the upper value of the [Trim In Select] selection when the source
is an analog input.
Default:
Min/Max:
Units:
60.0 Hz
–/+[Maximum Speed]
0.1 Hz
082
,
117
120
[Trim Lo]
Scales the lower value of the [Trim In Select] selection when the source is
an analog input.
Default:
Min/Max:
Units:
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
117
Slip Comp
Important: Parameters in the Slip Comp Group are used to enable and tune the Slip Compensation Regulator. In order
to allow the Slip Compensation Regulator to control drive operation, parameter 080 [Speed Mode] must be set to 1 “Slip
Comp”.
121
[Slip RPM @ FLA]
Sets the amount of compensation to drive output at motor FLA.
If the value of parameter 061 [Autotune] = 3 “Calculate,” changes made to
this parameter will not be accepted.
Default:
Min/Max:
Units:
Based on [Motor NP RPM]
0.0/1200.0 RPM
0.1 RPM
,
080
,
122
,
123
122
[Slip Comp Gain]
Sets the response time of slip compensation.
Default:
Min/Max:
Units:
40.0
1.0/100.0
0.1
080
,
121
,
122
123
[Slip RPM Meter]
Displays the present amount of adjustment being applied as slip
compensation.
Default:
Min/Max:
Units:
Read Only
0.0/300.0 RPM
0.1 RPM
080
,
121
,
122
Fil
e
Gr
oup
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Related
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Trimmed
0 =Not Trimmed
x =Reserved
Bit #
Factory Default Bit Values
Trim Ref A
Trim Ref B