Dynamic control file, Dynamic control file -15 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 63

Programming and Parameters
3-15
Dynamic Control File
Fil
e
Gr
oup
No.
Parameter Name & Description
for symbol descriptions
Values
Related
D
Y
NAMIC CO
NTR
O
L
Ramp Rates
140
141
[Accel Time 1]
[Accel Time 2]
Sets the rate of accel for all speed increases.
Default:
Min/Max:
Units:
10.0 Secs
10.0 Secs
0.1/3600.0 Secs
0.1 Secs
,
142
143
[Decel Time 1]
[Decel Time 2]
Sets the rate of decel for all speed decreases.
Default:
Min/Max:
Units:
10.0 Secs
10.0 Secs
0.1/3600.0 Secs
0.1 Secs
,
146
[S Curve %]
Sets the percentage of accel or decel time that is applied to the ramp as
S Curve. Time is added, 1/2 at the beginning and 1/2 at the end of the
ramp.
Default:
Min/Max:
Units:
0%
0/100%
1%
thru
Loa
d Limits
147
[Current Lmt Sel]
Selects the source for the adjustment of current limit (i.e. parameter,
analog input, etc.).
Default:
Options:
0
0
1
2
“Cur Lim Val”
“Cur Lim Val”
“Analog In 1”
“Analog In 2”
148
[Current Lmt Val]
Defines the current limit value when [Current Lmt Sel] = “Cur Lim Val.”
Default:
Min/Max:
Units:
[Rated Amps]
× 1.5
(Equation yields approximate default
value.)
Based on Drive Rating
0.1 Amps
149
[Current Lmt Gain]
Sets the responsiveness of the current limit.
Default:
Min/Max:
Units:
250
0/5000
1
150
[Drive OL Mode]
Selects the drive’s response to increasing drive temperature.
Default:
Options:
3
0
1
2
3
“Both–PWM 1st”
“Disabled”
“Reduce CLim”
“Reduce PWM”
“Both–PWM 1st”
219
151
[PWM Frequency]
Sets the carrier frequency for the PWM output.
Default:
Min/Max:
Units:
4 kHz
2/4 kHz
1 kHz
Stop/Bra
ke Modes
155
156
[Stop Mode A]
[Stop Mode B]
Active stop mode. [Stop Mode A] is active unless [Stop Mode B] is
selected by inputs.
(1)
When using options 1 or 2, read this Attention statement.
Default:
Default:
Options:
1
0
0
1
2
3
“Ramp”
“Coast”
“Coast”
“Ramp”
(1)
“Ramp to Hold”
(1)
“DC Brake”
,
157
[DC Brake Lvl Sel]
Not available.
158
[DC Brake Level]
Not available.
159
[DC Brake Time]
Not available.
160
[Bus Reg Ki]
Sets the responsiveness of the bus regulator.
Default:
Min/Max:
Units:
450
0/5000
1
Max Speed
Accel Time
Accel Rate
=
Max Speed
Decel Time
Decel Rate
=
!
ATTENTION: If a hazard of injury due to movement of equipment or material exists, an auxiliary
mechanical braking device must be used.