Start-up routines, Start-up routines -3 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 47

Start Up
2-3
Start-Up Routines
The LPM15 is designed so that start up is simple and efficient. If you have
an LCD HIM, two start-up methods are provided, allowing the user to select
the desired level needed for the application.
• S.M.A.R.T. Start
This routine allows you to quickly set up the drive by programming
values for the most commonly used functions. See
.
• Assisted Start Up
This routine prompts you for information that is needed to start up a
drive for most applications, such as line and motor data, commonly
adjusted parameters and I/O. See
.
Figure 2.2 Standard Control Option Start Up Menu
Important Information
Power must be applied to the drive when viewing or changing parameters.
Previous programming may affect the drive status and operation when
power is applied.
Configure for
Alternate Input
Voltage
Input Voltage
Start-Up
Enter Motor NP
Data, Stop Mode,
Accel/Decel
Ramp Times
Motor Data and
Ramp Times
Optimize Torque
and
Verify Direction
Motor Tests
Set Min/Max
Speed and
Direction Control
Speed Limits
Configure
Source, Value
and Scale for
Speed References
Speed Control
Start/Stop/I/O
Configure
Control Method
(2 Wire/3 Wire), I/O,
Digital Inputs/Outputs
and Analog Outputs
Done /
Exit
Main Menu:
(1)
(1)
During Motor Tests and tuning procedures, the drive may modify certain parameter values for proper Start Up operation.
These values are then reset to their original values when Start Up is complete. The affected parameters are: 053, 080,
276, 278, and 361-366. If power is removed from the drive during the tests without aborting the auto-tune procedure,
these parameters may not be reset to their original value. If this situation occurs, reset the drive to factory defaults and
repeat the Start Up procedure.