Utility file, Utility file -19 – Rockwell Automation 20M LPM15 Liquid-Cooled Adjustable Frequency AC Drive FRN 2.xxx User Manual
Page 67

Programming and Parameters
3-19
Utility File
Fil
e
Gr
oup
No.
Parameter Name & Description
for symbol descriptions
Values
Related
UTI
L
ITY
Direction Config
190
[Direction Mode]
Selects the method for changing drive direction.
Default:
Options:
0
0
1
2
“Unipolar”
“Unipolar”
“Bipolar”
“Reverse Dis”
thru
thru
HIM Ref Config
192
[Save HIM Ref]
Enables a feature to save the present frequency reference value issued by the HIM to Drive memory on power loss.
Value is restored to the HIM on power up.
193
[Man Ref Preload]
Enables/disables a feature to automatically load the present “Auto”
frequency reference value into the HIM when “Manual” is selected. Allows
smooth speed transition from “Auto” to “Manual.”
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
MOP Config
194
[Save MOP Ref]
Enables/disables the feature that saves the present MOP frequency reference at power down or at stop.
195
[MOP Rate]
Sets rate of change of the MOP reference in response to a digital input.
Default:
Min/Max:
Units:
1.0 Hz/s
0.2/[Maximum Freq]
0.1 Hz/s
Drive Memor
y
196
[Param Access Lvl]
Selects the parameter display level.
Basic = Reduced parameter set
Advanced = Full parameter set
Default:
Options:
0
0
1
2
“Basic”
“Basic”
“Advanced”
“Reserved”
197
[Reset To Defaults]
Resets parameters to factory defaults except [Language], [Param Access
Lvl], and [Voltage Class] (params. 196, 201, and 202).
• Option 1 resets parameters to factory defaults based on [Voltage
Class].
• Options 2 and 3 will reset parameters to factory defaults and set
[Voltage Class] to low or high voltage settings.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“Factory”
“Low Voltage”
“High Voltage”
thru
thru
082
198
[Load Frm Usr Set]
Loads a previously saved set of parameter values from a selected user
set location in drive nonvolatile memory to active drive memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
199
199
[Save To User Set]
Saves the parameter values in active drive memory to a user set in drive
nonvolatile memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
198
Mode
Direction Change
Unipolar
Drive Logic
Bipolar
Sign of Reference
Reverse Dis
Not Changeable
x
x
x
1
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Save at Power Down
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At P
owr Do
wn
0
x
x
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1 =Save at Power Down
0 =Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At P
owr Do
wn
At Stop