Accessories and dimensions b-3 – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 89
Accessories and Dimensions
B-3
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Table B.D Bulletin 1321-3R Series Line Reactors
Table B.E DC Bus Inductors
Input Voltage
kW
HP
Fundamental
Amps
Maximum
Continuous
Amps
Inductance
Watts
Loss
Catalog
Number
(1)
(1)
Catalog numbers listed are for 3% impedance open style units. NEMA Type 1 and 5% impedance
reactor types are also available. Refer to publication 1321-TD001….
240V 50/60 Hz
3-Phase
0.2
0.25
2
3
12.0 mh
7.5 W
1321-3R2-A
0.4
0.5
4
6
12.0 mh
21 W
1321-3R4-D
0.75
1.0
8
12
3.0 mh
29 W
1321-3R8-B
1.5
2.0
8
12
1.5 mh
19.5 W
1321-3R8-A
2.2
3.0
12
18
1.25 mh
26 W
1321-3R12-A
3.7
5.0
18
27
0.5 mh
36 W
1321-3R18-A
5.5
7.5
25
37.5
0.5 mh
48 W
1321-3R25-A
7.5
10.0
35
52.5
0.4 mh
49 W
1321-3R35-A
480V 50/60 Hz
3-Phase
0.4
0.5
2
3
20.0 mh
11.3 W
1321-3R2-B
0.75
1.0
4
6
9.0 mh
20 W
1321-3R4-C
1.5
2.0
4
6
6.5 mh
20 W
1321-3R4-B
2.2
3.0
8
12
5.0 mh
25.3 W
1321-3R8-C
3.7
5.0
12
18
2.5 mh
31 W
1321-3R12-B
5.5
7.5
12
18
2.5 mh
31 W
1321-3R12-B
7.5
10.0
18
27
1.5 mh
43 W
1321-3R18-B
11.0
15.0
25
37.5
1.2 mh
52 W
1321-3R25-B
Input Voltage
kW
HP
Amps
Inductance
mh
MTE Catalog Number
(2)
240V 50/60 Hz
3-Phase
5.5
7.5
32
0.85
32RB001
7.5
10.0
40
0.5
40RB001
480V 50/60 Hz
3-Phase
5.5
7.5
18
3.75
18RB004
7.5
10.0
25
4.0
25RB005
11.0
15.0
32
2.68
32RB003
(2)
Use MTE RB Series or equivalent inductors.