Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 14

1-4
Installation/Wiring
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Figure 1.2 Phase to Ground MOV Removal
Input Power Conditioning
The drive is suitable for direct connection to input power within the rated
voltage of the drive (see
are certain
input power conditions which may cause component damage or
reduction in product life. If any of the conditions exist, as described in
, install one of the devices listed under the heading Corrective
Action on the line side of the drive.
Important: Only one device per branch circuit is required. It should be
mounted closest to the branch and sized to handle the total
current of the branch circuit.
Table 1.C Input Power Conditions
Input Power Condition
Corrective Action
Low Line Impedance (less than 1% line reactance)
•
Install Line Reactor
(1)
•
or Isolation Transformer
(1)
Refer to
for accessory ordering information.
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
Line has frequent power interruptions
Line has intermittent noise spikes in excess of
6000V (lightning)
Phase to ground voltage exceeds 125% of normal
line to line voltage
•
Remove MOV jumper to ground.
•
or Install Isolation Transformer
with grounded secondary if
necessary.
Ungrounded distribution system
R/L1
S/L2
T/L3
1
2
3
4
Three-Phase
AC Input
Jumper