Basic program group, Basic program group -8, P104 – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 48: P105, P101
3-8
Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Basic Program Group
P101 [Motor NP Volts]
Related Parameter(s):
Stop drive before changing this parameter.
Set to the motor nameplate rated voltage.
Values
Default
Based on Drive Rating
Min/Max:
20/Drive Rated Voltage
Display:
1 VAC
P102 [Motor NP Hertz]
Related Parameter(s):
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values
Default
60 Hz
Min/Max:
10/400 Hz
Display:
1 Hz
P103 [Motor OL Current]
Related Parameter(s):
,
Set to the maximum allowable motor current.
The drive will fault on an F7 Motor Overload if the value of this parameter is exceeded by 150% for 60
seconds or 200% for 3 seconds.
Values
Default
Based on Drive Rating
Min/Max:
0.0/(Drive Rated Amps
×
2)
Display:
0.1 Amps
P104 [Minimum Freq]
Related Parameter(s):
,
Sets the lowest frequency the drive will output continuously.
Values
Default
0.0 Hz
Min/Max:
0.0/400.0 Hz
Display:
0.1 Hz
P105 [Maximum Freq]
Related Parameter(s):
,
,
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values
Default
60 Hz
Min/Max:
0/400 Hz
Display:
1 Hz