Common symptoms and corrective actions – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 77
![background image](/manuals/576950/77/background.png)
Troubleshooting
4-5
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Motor does not Start.
Drive does not Start from Integral Keypad.
Common Symptoms and Corrective Actions
Cause(s)
Indication
Corrective Action
No output voltage to the motor.
None
Check the power circuit.
•
Check the supply voltage.
•
Check all fuses and disconnects.
Check the motor.
•
Verify that the motor is
connected properly.
Check the control input signals.
•
Verify that a Start signal is
present. If 2-Wire control is used,
verify that either the Run
Forward or Run Reverse signal
is active, but not both.
•
Verify that I/O Terminal 01 is
active.
•
[Start Source]
matches your configuration.
•
[Reverse
Disable] is not prohibiting
movement.
Improper boost setting at initial
start-up.
None
Set
[Boost Select] to option 2
“35.0, VT”.
Drive is Faulted
Flashing red status light
Clear fault.
•
Press Stop
•
Cycle power
•
[Fault Clear] to option 1
“Clear Faults”.
•
[Digital Inx Sel] is set to option 7
“Clear Fault”.
Cause(s)
Indication
Corrective Action
Integral keypad is not enabled. Green LED above Start key is
not illuminated.
•
Set parameter
[Start
Source] to option 0 “Keypad”.
•
-
[Digital
Inx Select] to option 5 “Local”
and activate the input.
I/O Terminal 01 “Stop” input is
not present.
None
Wire inputs correctly and/or install
jumper.