Essential Requirements for CE Compliance
Conditions 1-3 listed below must be satisfied for PowerFlex drives to
meet the requirements of EN61800-3.
1. Grounding as described in
. Refer to
for
additional grounding recommendations.
2. Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
3. Allowable cable length in
is not exceeded.
Table 1.I Allowable Cable Length
(1)
for details on optional external filters.
(2)
Equivalent to EN55011 Class A.
(3)
Equivalent to EN55011 Class B.
Figure 1.6 Connections and Grounding
(1)
First Environment Unrestricted Distribution installations require a shielded enclosure.
Keep wire length as short as possible between the enclosure entry point and the EMI
filter.
(2)
Integral EMI filters are available on 240V, 1-Phase drives and 380V, 3-Phase drives.
Filter Type
EN61800-3
Second
Environment
EN61800-3 First
Environment
Restricted
Distribution
(2)
EN61800-3 First
Environment
Unrestricted
Distribution
(3)
Integral, 240V
5 meters (16 feet)
5 meters (16 feet)
1 meter (3 feet)
Integral, 480V
10 meters (33 feet)
–
–
External - S Type
(1)
5 meters (16 feet)
5 meters (16 feet)
1 meter (3 feet)
External - L Type
(1)
100 meters (328 feet) 100 meters (328 feet) 25 meters (82 feet)