Essential Requirements for CE Compliance

Conditions 1-3 listed below must be satisfied for PowerFlex drives to
meet the requirements of EN61800-3.

1. Grounding as described in

Figure 1.6

. Refer to

page 1-6

for

additional grounding recommendations.

2. Output power, control (I/O) and signal wiring must be braided,

shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.

3. Allowable cable length in

Table 1.I

is not exceeded.

Table 1.I Allowable Cable Length

(1)

Refer to

Appendix B

for details on optional external filters.

(2)

Equivalent to EN55011 Class A.

(3)

Equivalent to EN55011 Class B.

Figure 1.6 Connections and Grounding

(1)

First Environment Unrestricted Distribution installations require a shielded enclosure.
Keep wire length as short as possible between the enclosure entry point and the EMI
filter.

(2)

Integral EMI filters are available on 240V, 1-Phase drives and 380V, 3-Phase drives.

Filter Type

EN61800-3
Second
Environment

EN61800-3 First
Environment
Restricted
Distribution

(2)

EN61800-3 First
Environment
Unrestricted
Distribution

(3)

Integral, 240V

5 meters (16 feet)

5 meters (16 feet)

1 meter (3 feet)

Integral, 480V

10 meters (33 feet)

External - S Type

(1)

5 meters (16 feet)

5 meters (16 feet)

1 meter (3 feet)

External - L Type

(1)

100 meters (328 feet) 100 meters (328 feet) 25 meters (82 feet)

U/T1

V/T2

W/T3

EMI Fittings and Metal Conduit

Shielded Enclosure

(1)

Building Structure Steel

Enclosure Ground Connection

R/L1

S/L2

T/L3

(2)

EMI Filter

L1'

L2'

L3'

L1

L2

L3

Shielded Motor Cable

Esc

Sel