T211, T212, T213 – Rockwell Automation 22F PowerFlex 4M User Manual FRN 1.xx - 2.xx User Manual
Page 54

3-14
Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
t201 &
t202
Options
(Cont.)
13 “10V In Ctrl”
Selects 0-10V or ±10V control as the frequency reference.
Start source is not changed.
14 “20mA In Ctrl”
Selects 4-20mA control as the frequency reference. Start
source is not changed.
15 “Anlg Invert”
Inverts the scaling of the analog input levels set in
[Anlg In 0-10V Lo] and
[Anlg In 0-10V Hi] or
[Anlg In4-20mA Hi].
16-27
Reserved
t211 [Anlg In 0-10V Lo]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Minimum Freq] if a 0-10V input is used by
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than
[Anlg In 0-10V Hi] or by
setting
[Digital Inx Sel] to option 15 “Anlg Invert”.
Values
Default
0.0%
Min/Max:
0.0/ 100.0%
Display:
0.1%
0
P105 [Maximum Freq]
P104 [Minimum Freq]
t211 [Anlg In 0-10V Lo]
t212 [Anlg In 0-10V Hi]
0
Speed Ref
erence
t212 [Anlg In 0-10V Hi]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Maximum Freq] if a 0-10V input is used by
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than
[Anlg In 0-10V Lo] or by
setting
[Digital Inx Sel] to option 15 “Anlg Invert”.
Values
Default
100.0%
Min/Max:
0.0/ 100.0%
Display:
0.1%
t213 [Anlg In4-20mA Lo]
Related Parameter(s):
,
,
Sets the analog input level that corresponds to
[Minimum Freq] if a 4-20mA input is used by
[Speed Reference].
Analog inversion can be accomplished by setting this value larger than
[Anlg In4-20mA Hi] or by
setting
[Digital Inx Sel] to option 15 “Anlg Invert”.
Values
Default
0.0%
Min/Max:
0.0/ 100.0%
Display:
0.1%