background image

3-4

Programming and Parameters

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E

Display Group

(continued)

d006 [Drive Status]

Related Parameter(s):

A434

Present operating condition of the drive.

Values

Default

Read Only

Min/Max:

0/1

Display:

1

1 = Condition True, 0 = Condition False

Running

Bit 0

Forward

Bit 1

Accelerating

Bit 2

Decelerating

Bit 3

d007 [Fault 1 Code]
d008 [Fault 2 Code]
d009 [Fault 3 Code]

A code that represents a drive fault. The codes will appear in these parameters in the order they occur
(

d007

[Fault 1 Code] = the most recent fault). Repetitive faults will only be recorded once.

Refer to

Chapter 4

for fault code descriptions.

Values

Default

Read Only

Min/Max:

F2/F122

Display:

F1

d010 [Process Display]

Related Parameter(s):

d001

,

A440

,

A438

,

A439

32 bit parameter.

The output frequency scaled by

A440

[Process Factor] or by

A438

[Process Time Lo] and

A439

[Process Time Hi].

Values

Default

Read Only

Min/Max:

0.00/9999

Display:

0.01 – 1

32

Output

Freq

Process

Factor

Process

Display

=

x