Motor and/or drive will not accelerate to commanded speed.

Motor operation is unstable.

Drive will not reverse motor direction.

Drive does not power up.

Cause(s)

Indication

Corrective Action

Acceleration time is excessive. None

Reprogram

P109

[Accel Time 1] or

A401

[Accel Time 2].

Excess load or short
acceleration times force the
drive into current limit, slowing
or stopping acceleration.

None

Compare

d003

[Output Current] with

A441

[Current Limit].

Remove excess load or reprogram

P109

[Accel Time 1] or

A401

[Accel

Time 2].
Check for improper

A453

[Boost

Select] setting.

Speed command source or
value is not as expected.

None

Verify

d002

[Commanded Freq].

Check

d012

[Control Source] for the

proper Speed Command.

Programming is preventing the
drive output from exceeding
limiting values.

None

Check

P105

[Maximum Freq] to

insure that speed is not limited by
programming.

Cause(s)

Indication

Corrective Action

Motor data was incorrectly
entered.

None

1. Correctly enter motor nameplate

data into

P101

,

P102

and

P103

.

2. Enable

A436

[Compensation].

3. Use

A453

[Boost Select] to

reduce boost level.

Cause(s)

Indication

Corrective Action

Digital input is not selected for
reversing control.

None

Check [Digital Inx Sel]

(See

page 3-13)

. Choose correct input

and program for reversing mode.

Digital input is incorrectly
wired.

None

Check input wiring.

(See page 1-14)

Motor wiring is improperly
phased for reverse.

None

Switch two motor leads.

Reverse is disabled.

None

Check

A434

[Reverse Disable].

Cause(s)

Indication

Corrective Action

No input power to drive.

None

Check the power circuit.

Check the supply voltage.

Check all fuses and disconnects.

Jumper between I/O Terminals
P2 and P1 not installed and/or
DC Bus Inductor not
connected.

None

Install jumper or connect DC Bus
Inductor.