Troubleshooting
4-7
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Motor and/or drive will not accelerate to commanded speed.
Motor operation is unstable.
Drive will not reverse motor direction.
Drive does not power up.
Cause(s)
Indication
Corrective Action
Acceleration time is excessive. None
Reprogram
[Accel Time 1] or
[Accel Time 2].
Excess load or short
acceleration times force the
drive into current limit, slowing
or stopping acceleration.
None
Compare
[Output Current] with
[Current Limit].
Remove excess load or reprogram
[Accel Time 1] or
[Accel
Time 2].
Check for improper
[Boost
Select] setting.
Speed command source or
value is not as expected.
None
Verify
[Commanded Freq].
Check
[Control Source] for the
proper Speed Command.
Programming is preventing the
drive output from exceeding
limiting values.
None
Check
[Maximum Freq] to
insure that speed is not limited by
programming.
Cause(s)
Indication
Corrective Action
Motor data was incorrectly
entered.
None
1. Correctly enter motor nameplate
data into
,
.
2. Enable
[Compensation].
3. Use
[Boost Select] to
reduce boost level.
Cause(s)
Indication
Corrective Action
Digital input is not selected for
reversing control.
None
. Choose correct input
and program for reversing mode.
Digital input is incorrectly
wired.
None
Check input wiring.
Motor wiring is improperly
phased for reverse.
None
Switch two motor leads.
Reverse is disabled.
None
Check
[Reverse Disable].
Cause(s)
Indication
Corrective Action
No input power to drive.
None
Check the power circuit.
•
Check the supply voltage.
•
Check all fuses and disconnects.
Jumper between I/O Terminals
P2 and P1 not installed and/or
DC Bus Inductor not
connected.
None
Install jumper or connect DC Bus
Inductor.