Programming and Parameters

3-17

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Communications Group

C301 [Language]

Selects the language displayed by the remote communications option.

Options

1 “English” (Default)

2 “Second Lang” (Reserved)

C302 [Comm Data Rate]

Related Parameter(s):

d015

Sets the serial port rate for the RS485 (DSI) port.

Important: Power to drive must be cycled before any changes will affect drive operation.

Options

0 “1200”

1 “2400”

2 “4800”

3 “9600” (Default)

4 “19.2K”

5 “38.4K”

C303 [Comm Node Addr]

Related Parameter(s):

d015

Sets the drive node address for the RS485 (DSI) port if using a network connection.

Important: Power to drive must be cycled before any changes will affect drive operation.

Values

Default

100

Min/Max:

1/247

Display:

1

C304 [Comm Loss Action]

Related Parameter(s):

d015

,

P107

,

C305

Selects the drive’s response to a loss of the communication connection or excessive communication
errors.

Options

0 “Fault” (Default)

Drive will fault on an F81 Comm Loss and coast to stop.

1 “Coast to Stop”

Stops drive via coast to stop.

2 “Stop”

Stops drive via

P107

[Stop Mode] setting.

3 “Continu Last”

Drive continues operating at communication commanded
speed saved in RAM.