Advanced Program Group
(continued)
A410 [Preset Freq 0]
(1)
A411 [Preset Freq 1]
A412 [Preset Freq 2]
A413 [Preset Freq 3]
Related Parameter(s):
,
,
,
Values
A410 Default
A411 Default
A412 Default
A413 Default
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
Min/Max:
0.0/400.0 Hz
Display:
0.1 Hz
Provides a fixed frequency command value when
[Digital Inx Sel] is set to 4 “Preset
Frequencies”.
An active preset input will override speed command as shown in the flowchart on
.
(1)
To activate
[Preset Freq 0] set
[Speed Reference] to option 4 “Preset Freq 0-3”.
Input State of Digital In 1
(I/O Terminal 05)
Input State of Digital In 2
(I/O Terminal 06)
Frequency Source
Accel / Decel Parameter Used
(2)
0
0
[Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
1
0
[Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
0
1
[Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
1
1
[Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in
this table.
A418 [Skip Frequency]
Related Parameter(s):
Sets the frequency at which the drive will not operate.
A setting of 0 disables this parameter.
Values
Default
0 Hz
Min/Max:
0/400 Hz
Display:
1 Hz