Programming and Parameters

3-15

PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual

Publication 22F-UM001D-EN-E

Terminal Block Group

(continued)

t214 [Anlg In4-20mA Hi]

Related Parameter(s):

d021

,

P105

,

P108

,

t201

,

t202

Sets the analog input level that corresponds to

P105

[Maximum Freq] if a 4-20mA input is used by

P108

[Speed Reference].

Analog inversion can be accomplished by setting this value smaller than

t213

[Anlg In4-20mA Lo] or

by setting

t201

-

t202

[Digital Inx Sel] to option 15 “Anlg Invert”.

Values

Default

100.0%

Min/Max:

0.0/ 100.0%

Display:

0.1%

t221 [Relay Out Sel]

Related Parameter(s):

P103

,

t222

,

A451

Sets the condition that changes the state of the output relay contacts.

Options

0 “Ready/Fault”

(Default)

Relay changes state when power is applied. This indicates
that the drive is ready for operation. Relay returns drive to
shelf state when power is removed or a fault occurs.

1 “At Frequency”

Drive reaches commanded frequency.

2 “MotorRunning”

Motor is receiving power from the drive.

3 “Reverse”

Drive is commanded to run in reverse direction.

4 “Motor Overld”

Motor overload condition exists.

5 “Ramp Reg”

Ramp regulator is modifying the programmed accel/decel
times to avoid an overcurrent or overvoltage fault from
occurring.

6 “Above Freq”

Drive exceeds the frequency (Hz) value set in

t222

[Relay Out

Level].

7 “Above Cur”

Drive exceeds the current (% Amps) value set in

t222

[Relay

Out Level].

Important: Value for

t222

[Relay Out Level] must be entered

in percent of drive rated output current.

8 “Above DCVolt”

Drive exceeds the DC bus voltage value set in

t222

[Relay

Out Level].

9 “Retries Exst”

Value set in

A451

[Auto Rstrt Tries] is exceeded.

10 “Above Anlg V”

Analog input voltage (I/O Terminal 13) exceeds the value
set in

t222

[Relay Out Level].

This parameter setting can also be used to indicate a PTC
trip point when the input (I/O Terminal 13) is wired to a
PTC and external resistor.

Use

t222

to set threshold.

11 “ParamControl”

Enables the output to be controlled over network
communications by writing to

t222

[Relay Out Level].

(0 = Off, 1 = On.)

12 “NonRec Fault””

Value set in

A451

[Auto Rstrt Tries] is exceeded.

A451

[Auto Rstrt Tries] is not enabled.

A Non-resettable fault has occurred.

13 “I/O Control”

Enables the output to be controlled by bit 6 of the logic
command word. See

Writing (06) Logic Command Data on

page C-4

for more information.

14-22

Reserved