Advanced Program Group

(continued)

A450 [Fault Clear]

Stop drive before changing this parameter.

Resets a fault and clears the fault queue. Used primarily to clear a fault over network communications.

Options

0 “Ready/Idle” (Default)

1 “Reset Fault”

2 “Clear Buffer”

(Parameters

d007

-

d009

[Fault x Code])

A451 [Auto Rstrt Tries]

Sets the maximum number of times the drive attempts to reset a fault and restart.
Clear a Type 1 fault and restart the drive.
1. Set

A451

[Auto Rstrt Tries] to a value other than “0”.

2. Set

A452

[Auto Rstrt Delay] to a value other than “0”.

Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault without restarting the drive.
1. Set

A451

[Auto Rstrt Tries] to a value other than “0”.

2. Set

A452

[Auto Rstrt Delay] to “0”.

Values

Default

0

Min/Max:

0/9

Display:

1

!

ATTENTION:

Equipment damage and/or personal injury may result if this parameter

is used in an inappropriate application. Do not use this function without considering
applicable local, national and international codes, standards, regulations or industry
guidelines.

A452 [Auto Rstrt Delay]

Related Parameter(s):

A451

Sets the time between restart attempts when

A451

[Auto Rstrt Tries] is set to a value other than zero.

Values

Default

1.0 Secs

Min/Max:

0.0/120.0 Secs

Display:

0.1 Secs