Sensaphone IMS-1000 Users manual User Manual
Page 98
IMS-1000 Manual
98
PULSE/AUTO: Pulse Count Jumper
Jumper in position 1 (to the right): Jumper setting for a stable environment without air drafts.
Jumper in position AUTO (to the left): Setting for a harsh environment.
Figure 2: Sensitivity adjustment and jumper locations
Sensor Template (factory default)
Input Name:
Motion Detector
Recognition Time:
1 Second
Reset Time:
0 Seconds
Data Logging:
Active
Voice:
motion detector.wav
Input Class:
Other
Specifications
Pyrosensor:
Dual element type
Power Input: 8.2–16 Vdc
Current Consumption: 8mA @ 12 Vdc
Temperature Compensation:
Yes
Alarm Period: 2 sec (± 5sec)
Alarm Output: N.C. 100mA @ 28 Vdc
(10W in line resistor Form “A”)
Tamper Switch:
N.C. 100mA @28 Vdc
(10W in line resistor Form “A”)-open
Operating ambient temperature range:
-4ºF to +140ºF (-20ºC to +60ºC)
Operating humidity range:
Up to 95% (non-condensing)
Storage temperature range:
-40ºF to +176ºF (-40ºC to +80ºC)
RFI protection:
≥30 V/m @ 10-1000 MHz
EMI immunity:
50,000 V electrical interference
Dimensions:
3.8'' x 1.8'' x2.5'' (97mm x 63mm x 46.5mm)
Weight: 3 oz (85 grams)