Alarm logic – Sensaphone IMS-1000 Users manual User Manual
Page 39
Chapter 2: Configuration
39
Normal Data Log Interval: This is the time interval that data will be logged while the IP device is
responding.
Alarm Data Log Interval: This is the time interval that data will be logged while the IP device is
not responding.
Alarm Logic
Network devices are monitored by the IMS-1000 by pinging/connecting to programmed IP
addresses on a programmable interval. The unit will only attempt to ping/connect to devices which
are Enabled. Each time the network device responds, the IMS-1000 updates the Last Response time.
A time limit for responding is assigned to each IP Alarm to determine if the device is functioning
properly. This time limit is called the alarm Timeout. If a network device does not respond within
this time period, the IMS-1000 will count this as a ping failure. You can program the IMS-1000 to
try to ping/connect to the network device several times before tripping an alarm. The ping Retries
deter mines how many times the IMS-1000 will try to ping/connect to the device before sending an
alarm. An alarm will only occur if the device fails to respond to consecutive ping attempts. Once
a successful response is received, the failure counter will reset. For example: If the ping Retries is
set to 3, then the IMS-1000 must fail to ping/connect to the device 4 times in a row (initial attempt
+ 3 retries) to trip an alarm. If the device were to respond after the second attempt, then the failure
counter would reset, thus requiring four subsequent successive failures to trip an alarm. Once an
alarm is recognized, the Last Alarm time will be updated.
A dependency device (IP address) can be programmed for each IP Alarm. This is used to prevent
numerous alarms from occurring when common network infrastructure problems arise. If the
dependency device fails, then all IP alarms that have this dependency will be temporarily disabled
from sending alarms until the dependency device returns to normal (e.g. starts responding to ping/
connect requests). When an IP Alarm’s dependency is not responding, the status for the IP Alarm
will be shown as “Route Down.” It is recommended that the dependency device be programmed
such that it will go into alarm before any other devices. You can achieve this by setting the number
of Retries for the dependency device to a lower value than the IP Alarms which rely on this device.
In summary, for an IP Alarm to be dispatched, the following criteria must be met:
a) The IP Alarm must be enabled.
b) Alarm deliveries must be enabled.
c) It must have failed to respond to consecutive ping/connect requests and exceed the number of
retries.
d) There must be one or more User Profiles with Contacts.
Once the alarm is dispatched, the alarm delivery process begins. The Last Acknowledgement time
will update when the alarm has been acknowledged. In the case where there are no voice contacts,
the Last Acknowledgement time will update immediately after the alarm occurs.
Additionally, there is an option to re-dispatch the alarm if it remains in an alarm state too long. This
programmable time period is called the Alarm Reset Time. This parameter can be set from 30 to
3600 minutes. For example: Suppose the Alarm Reset Time is set to 180 minutes. Now suppose an
IP device has stopped responding and trips an alarm which results in all programmed users receiv-
ing their respective messages. If the IP device continues to remain unresponsive for 180 minutes,
then the alarm will be dispatched again and everyone will be contacted once more.