Configuration, Sensor template (factory default), Specifications – Sensaphone IMS-1000 Users manual User Manual
Page 86
IMS-1000 Manual
86
6.732
2.166
Figure 2: Mounting the sensor
Configuration
All IMS Solution sensors are auto-configured when you plug them into the IMS-1000. The 20A
Current Sensor will identify itself as a 4-20mA transducer. On the Properties screen for this sensor
you must select the sensor type: Current Sensor. When a sensor is removed, or the connection is
disrupted, the configuration data remains intact but the sensor will go into trouble status and gener-
ate a trouble alarm. When the sensor is plugged in again, or the connection is re-established, con-
figuration data remains unchanged and the sensor returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.
Sensor Template (factory default)
Input Name: Transducer
High Limit: 100
Low Limit: 0
Recognition Time: 60 Seconds
Reset Time: 0 Seconds
Data Logging: Active
Voice: none
Input Class: Other
Specifications
Range: 0-20 Amps (0–250 VAC, 50/60 Hz)
Operating Temperature: 5-104 deg F (-15 to 40 deg C)
Operating Humidity: 0 to 95% RH, non-condensing
Accuracy: ± 2% (from 1-100% of full-scale output)
Power Connection: IEC320-C20 inlet/IEC320-C19 outlet
IMS Connection: RJ-45
Housing: Black plastic with mounting ears