Configuration
All IMS Solution sensors are auto-configured when you plug them into the IMS-1000. When a
new sensor is plugged into the IMS-1000, the configuration is set to the factory default via the
Sensor Template. If you have modified these templates, the configuration will be set to the modi-
fied configuration. When a sensor is removed, or the connection is disrupted, the configuration
data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains
unchanged and the sensor returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different sen-
sor at any time will cause a trouble alarm.
Sensor Template (factory default)
Input Name:
Humidity
Low Limit:
20%
High Limit:
60%
Recognition Time:
60 Seconds
Reset Time:
0 Seconds
Data Logging:
Active
Voice: humidity.wav
Input Class:
Humidity
Specifications
Range: 0–100% RH
Temperature: 32–122º F (0–50º C)
Accuracy:
+/- 5%
Connector:
RJ-45
Housing:
white plastic