beautypg.com

Sensaphone IMS-1000 Users manual User Manual

Page 64

background image

IMS-1000 Manual

64

Sensor Template (factory default)

Input Name:

Temperature

Low Temperature Limit:

50º F

High Temperature Limit:

85º F

Recognition Time:

60 Seconds

Reset Time:

0 Seconds

Data Logging:

Active

Voice: temperature.wav

Input Class:

Temperature

Specifications

Range:

5–140 degrees F

Humidity: 5–90% RH

Sensor type: solid state ic

Accuracy:

+/- 3 degrees F

Connector: 7' cable w/RJ-45 plug

Housing: black plastic

Housing dimensions: 2.13'' l x 0.6'' d x 1.38'' h