Sensaphone IMS-1000 Users manual User Manual
Page 64
IMS-1000 Manual
64
Sensor Template (factory default)
Input Name:
Temperature
Low Temperature Limit:
50º F
High Temperature Limit:
85º F
Recognition Time:
60 Seconds
Reset Time:
0 Seconds
Data Logging:
Active
Voice: temperature.wav
Input Class:
Temperature
Specifications
Range:
5–140 degrees F
Humidity: 5–90% RH
Sensor type: solid state ic
Accuracy:
+/- 3 degrees F
Connector: 7' cable w/RJ-45 plug
Housing: black plastic
Housing dimensions: 2.13'' l x 0.6'' d x 1.38'' h