Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.

Sensor Template (factory default)

Input Name: Transducer

Recognition Time: 3 Seconds

Reset Time: 0 Seconds

Data Logging: Active

Voice: None

Input Class: Other

Specifications

Input: 4–20mA DC

Current Limit: 50mA

Input Impedance: Variable (1000W @ 4mA, 260W @ 20mA)

Accuracy: ± 0.25%

IMS Connection: RJ-45

Operating Temperature Range: 32–122 deg F (0–50 degC)

Housing: Black plastic with mounting ears