Sensaphone IMS-1000 Users manual User Manual
Page 67
Chapter 5: IMS-1000 Sensors
67
Configuration
All IMS Solution sensors are auto-configured when you plug them into the IMS-1000. When a
new sensor is plugged into the IMS-1000, the configuration is set to the factory default via the
Sensor Template.
If you have modified these templates, the configuration will be set to the modi-
fied configuration. When a sensor is removed, or the connection is disrupted, the configuration
data remains intact but the sensor will go into trouble status and generate a trouble alarm. When
the sensor is plugged in again, or the connection is re-established, configuration data remains
unchanged and the sensor returns to normal operating condition.
Caution: Removing a sensor for less than 60 seconds does not produce a trouble alarm.
Removing or unplugging a sensor for more than 60 seconds or plugging in a different
sensor at any time will cause a trouble alarm.
Sensor Template (factory default)
Input Name:
Temperature
Low Temperature Limit:
10º C
High Temperature Limit:
27º C
Recognition Time:
60 Seconds
Reset Time:
0 Seconds
Data Logging:
Active
Voice: temperature.wav
Input Class:
Temperature
Specifications
Range: 0 to 35 degrees C
Humidity: 5–90 %RH
Sensor type: solid state ic
Accuracy:
+/- 1.7 degrees C
Connector:
RJ-45
Housing:
white plastic