5 .9 aC power FaIlure reCognItIon tIme
The AC Power Failure Recognition Time is the length of time that AC elec-
tric power is off before a valid alarm is recognized and dial-out begins. The
default setting is 5 minutes, 0 seconds, but is programmable from 0 seconds
to a maximum of 540 minutes.
When AC power failure occurs, and throughout the programmed
Recognition Time, the Model 400 steadily repeats the message “the power
is off” at the unit’s installation site. There is no Call Delay programming
available for AC power failure. Immediately following Recognition Time,
the Model 400 begins the dial-out process to report power failure.
To cancel the power-failure message locally at the keypad (during or after
Recognition Time) press the ALARM CANCEL key on the Model 400 key-
pad. This action also cancels the dial-out process.
5 .9 .1 programmIng power FaIlure
reCognItIon tIme
1. Press SET.