Controlling the thermostat – Sensaphone 400 User Manual
Page 107
Chapter 8: Controlling the Output
105
Step 2: mount the Sensaphone 400.
Choose a location for your Sensaphone that allows for easy wiring to the
thermostat, such as near your heater/air conditioning system. Mount the
unit on a wall or flat on a desktop or table surface. Plug in the power sup-
ply and connect the telephone line.
Step 3: Connect cable from thermostat to Sensaphone 400.
This Sensaphone 400 has a terminal strip below the input/output wiring
door that will connect to the 12VDC power supply and X & C terminals
of the thermostat (See Figure 1). This connection is required to switch the
thermostat between normal and vacation modes. Run a two-conductor
cable from the thermostat to the Model 400. On the thermostat, connect
the red wire to the X (+) terminal, and the black wire to the C (-) terminal.
On the 400, connect the red wire to the NO terminal. Connect the black
wire to the negative wire from the power supply. Use a wire nut to complete
this connection. Connect the positive wire from the power supply to the
“C” terminal on the model 400.
— Rc
— Y
— G
— X
— C
12V
Thermostat
shielded accessory cable
12VDC
Power Supply
red
black
-
+
1 C
ZONES
2 C
3 C
4 C
NO C NC
— Rh
— W
+
-
Step 4: Program the Thermostat.
Refer to the manufacturers instructions for programming the thermostat.
Be sure to program settings for both normal and vacation modes.
Controlling the Thermostat
The operating mode of the thermostat (normal/vacation) can be controlled
at the Model 400 keypad or remotely via Touch-Tone comands. Both
methods are described below: