5 .3 zone recognition time, Press recognition time, The model 400 responds: “enter minutes – Sensaphone 400 User Manual
Page 72
70
SENSAPHONE 400 User’s Manual
For example, zone 3 is configured as a normally open, dry contact zone.
During the Status Report:
• If disabled, the Model 400 recites:
“Zone 3, the Alarm is Disabled” for zone 3.
• If enabled, the Model 400 recites:
“Zone 3—OK,” for zone 3.
In another example, zone 2 is configured as a temperature zone. The cur-
rent temperature is 76 degrees. During a Status Report:
• If disabled, the Model 400 recites:
“Zone 2, the alarm is disabled, it is now 76 degrees fahrenheit—OK”
• If enabled, the Model 400 recites:
“Zone 2—76 degrees fahrenheit—OK.”
5 .3 Zone reCognItIon tIme
The Zone Recognition Time is the length of time an alert condition
must be present before a valid alarm exists and dial-out is activated. This
time period is programmable, from 0 minutes, 0 seconds (for immediate
response) up to a period of 540 minutes, 0 seconds. If an alert condition
begins and then clears within the established Recognition Time, no dial-
out will occur. When an alert condition continues beyond the programmed
Recognition Time, the Model 400 initiates dial-out. The default setting for
Zone Recognition Time is 0 minutes, 3 seconds.
5 .3 .1 programmIng Zone reCognItIon tIme
1. Press SET.
SET
2. Press RECOGNITION TIME.
7
RECOGNITION
TIME
3. Press the number (1 to 4) of the selected zone to be programmed.
4
MAX CALLS
3
INTERCALL
TIME
1
CALL
DELAY
2
VOICE
REPS
The Model 400 responds: “Enter minutes.”