Sensaphone 400 User Manual
Page 118
116
SENSAPHONE 400 User’s Manual
other monItorIng
Problem
Cause
Solution
1. Alarm status of an
alert zone is incorrect.
Incorrect zone normality.
Reconfigure the zone.
Refer to Chapter 5, Section
5.1.
2. False power out
alarms
Programmed Recognition
Time is too short.
AC power is often sub-
ject to brief interruptions.
To avoid frequent, false
alarms, increase the power
Recognition Time. Refer to
Chapter 5, Section 5.9.
3. The Model 400 does
not recognize power
failure.
a) Batteries are either
incorrectly installed
or drained.
b) Recognition time
setting is too long.
To verify proper bat-
tery function, unplug the
unit and verify continued
operation using batteries
only. If unit ceases to
function, first try reinstall-
ing the batteries. If this is
not successful, replace the
batteries. Refer to Chapter
2, Section 2.4 for complete
instructions.
Reprogram Recognition
Time. Set the Recognition
Time to the minimum
required before a valid
alarm occurs. If pos-
sible, test the condition by
deliberately creating an
alert condition. Refer to
Chapter 5, Section 5.9.