Chapter 5: Alarm Programming
73
4. Using the number keys, enter a value for low temperature limit. The
Model 400 will recite the digits as they are pressed. If a negative number
is required, first press *, then enter the number.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS
5. Press ENTER.
ENTER
PM
The Model 400 responds: “Enter high temperature limit.”
6. Using the number keys, enter the value for high temperature limit. The
Model 400 recites the digits as they are pressed.
4
MAX CALLS
5
TEMP LIMITS
6
CALIBRATE
8
CLOCK
3
INTERCALL
TIME
7
RECOGNITION
TIME
9
LISTEN TIME
SOUND
0
ID NUMBER
POWER
1
CALL
DELAY
2
VOICE
REPS
7. Press ENTER. The Model 400 responds: “Enter.”
ENTER
PM
NOTE: Do not set temperature limits too close to normal room
temperature. Minor temperature fluctuations could result in frequent
and unnecessary alarm dialouts.