Appendix c: 400 quick reference, Parameter description key sequence* range default – Sensaphone 400 User Manual
Page 121
Appendix C: 400 QUICK REFERENCE
119
appendIx C: 400 QuICk referenCe
Parameter
Description
Key Sequence*
Range
Default
Call Delay
Time delay until
first call is made
[SET] or [WHAT IS]
+ [CALL DELAY]
Min: 00:00
Max 60:00
(min:sec)
00:30
(min:sec)
Voice Reps
Number of times alarm
message is repeated
over the phone
[SET] or [WHAT IS]
+ [VOICE REPS]
Min: 1 rep
Max: 10 reps
3 reps
Intercall Time
Time delay between
phone calls
[SET] or [WHAT IS] +
[INTERCALL TIME]
Min: 00:10
Max: 60:00
(min:sec)
01:00
(min:sec)
Max Calls
Number of calls until unit
self-acknowledges
[SET] or [WHAT IS] +
[MAX CALLS]
Min: 1 call
Max: 255 calls
100 calls
Temp Limits
High and low temperature
alarm limits
[SET] or [WHAT IS]
+ [TEMP LIMITS] +
[zone #]
Min: -20°F/-30°C
Max: 150°F/65°C
Low: 10°F
High:100°F
Calibrate
Temperature Correction
factor
[SET] or [WHAT IS] +
[CALIBRATE] +
[zone #]
Min: -10°
Max: 10°
0°
Recognition
Time:
zones 1–4
Length of time a
fault condition must exist
to trip an alarm
[SET] or [WHAT IS]+
[RECOGNITION
TIME]
Min: 00:00
Max: 540:00
(min:sec)
00:03
(min:sec)
Recognition
Time: Power
Failure
Length of time the
power must be off
to trip an alarm
[SET] or [WHAT IS]
+[RECOGNITION
TIME]+[POWER]
Min: 0:00
Max: 540:00
(min:sec)
05:00
(min:sec)
Recognition
Time: High
Sound Level
Length of time the
sound must be high
to trip an alarm
[SET] or [WHAT IS]
+[RECOGNITION
TIME]
Min: 5
Max: 60
(sec)
00:08
(min:sec)
Clock
Real time clock
[SET] or [WHAT IS]
+ [CLOCK] + [time] +
[AM] or [PM]
12:00
am
High Sound
Level Alarm
Sensitivity
Microphone sensitivity
for high sound
level alarm
[SET] or [WHAT IS]
+ [CALIBRATE] +
[SOUND]
Min: 1 unit
Max: 160 units
32 units
Listen Time
Length of listen-in time
during call-in status report
[SET] or [WHAT IS] +
[LISTEN TIME]
Min: 0 sec
Max: 255 sec
15 sec
Rings
Until Answer
Number of rings until unit
answers an incoming call
[SET] or [WHAT IS] +
[RING]
Min: 1 ring
Max: 15 rings
4 rings
* press [ENTER] after all Key Sequences starting with [SET]