Appendix B: Troubleshooting

115

Sound level monItorIng

Problem

Cause

Solution

1. False high sound

alarms occur
frequently.

The programmed sound
sensitivity results in over-
sensitivity to non-alarm
sound as well as alarm
sound.

Sound Recognition Time is
too short.

Reprogram the sound sen-
sitivity.
Refer to Chapter 5, Section
5.10.

Lengthen the sound
Recognition Time.
Refer to Chapter 5, Section
5.10.

2. High sound does not

cause an alarm.

The unit is not close
enough to the high sound
source, or the programmed
sound setting results in a
lack of sensitivity to high
sound.

Move the unit closer or
reprogram the sound sen-
sitivity.
Refer to Chapter 5, Section
5.10.