Wiring details & functions (all options shown), Jumper settings – SDC 1511T EXIT CHECK DELAYED EGRESS EMLOCK User Manual
Page 9
Wiring Details & Functions (ALL OPTIONS SHOWN)
P:\INSTALLATION INST\Delayed Egress\INST-1511ST\INST-1511ST.vsd Rev G3 10-13 Page 9
REQUEST TO EXIT
KEY SWITCH OR
ACCESS
CONTROL
SYSTEM
(OPTIONAL)
REMOTE RESET
SWITCH
(OPTIONAL)
REMOTE
STATUS PANEL
(OPTIONAL)
FIRE
ALARM
INPUT
(OPTIONAL)
POWER
SUPPLY
12VDC
OR 24VDC
Dry,
N/C
BLK
RMB X L3
RED
EXTERNAL
TRIGGER
SWITCH
OR
SDC REX PUSH BAR
(OPTIONAL)
DOOR POSITION
SWITCH
(DPS)
BOND ALERT (BAS)
[DPS]
[BAS]
N/O
COM
N/C
[ATS]
ANTI-TAMPER SWITCH
(ATS)
MONITORING OPTIONS
N/O
COM
N/C
N/O
COM
N/C
GRN
SMOKE DETECTION
SYSTEM INPUT
(OPTIONAL)
Dry,
N/C
INSTANT
BYPASS
OVERRIDE
(OPTIONAL)
TERMINAL BOARD CONNECTIONS
POWER IN -
POWER IN +
COM
N/C
AUX LOCK -
AUX LOCK +
N/O
COM
N/C
N/O
COM
N/C
N/O
COM
N/O
COM
N/O
COM
[PWR]
[FP]
[LOCK]
[GRN
RLY]
[RED
RLY]
[RM
TRIG]
[RESET]
[REX]
12 VDC OR 24 VDC
TO CLOSED FIRE/SMOKE
DETECTOR CONTACT
SLAVE/TANDEM LOCK
POWER TERMINALS
LOCK SECURE
OUTPUT
ALARM OUTPUT
EXTERNAL TRIGGER
SWITCH INPUT
EXTERNAL RESET
SWITCH INPUT
REQUEST TO EXIT
INPUT
[IBO]
INSTANT BYPASS OVERRIDE
INPUT
N/O
COM
JUMPER
J6
C NC
-
+
-
+
NC NO
NO C
C NC
NO C
NO C
NO C NO C
NO C NC NO C NC
[ BAS ]
[ DPS ]
[RESET]
[RM TRIG]
[REX]
[RED RLY]
[GRN RLY]
[ LOCK ]
[ FP ]
[ PWR ]
J6
J7
J2
[IBO]
[EXT SPKR]
REMOTE
SPEAKER
(OPTIONAL)
JUMPER
J7
JUMPER SETTINGS
JUMPER J6 (Fire Alarm Input) – Factory Installed. Remove
J6 only if a dry, normally closed contact from a fire alarm OR
smoke detector system is connected to the Fire Panel [FP]
terminals.
INSTALLED: The ExitCheck™ will enter the alarm mode if the
door is held open past the request to exit period.
REMOVED: The ExitCheck™ will remain unlocked if the door
is held open past the request to exit period. No alarm will
sound. The ExitCheck™ will relock and rearm upon closure of
the door.
JUMPER J7 (DOOR PROP)