2111 interbus fieldbus module – Lenze EMF2111IB User Manual
Page 69

Data transfer
Configuration of the parameter data channel (PCP communication)
5
2111 INTERBUS fieldbus module
5.6
5.6.8
L
5.6-47
EDSIBS-1.0-06/2003
Lenze parameter sets
Parameter sets are for special code saving which is necessary because of
different configurations for different application processes.
The following table informs about number and addressing of parameter sets for
your controller:
82XX
8200 vector
93XX
The 82XX and 8200 vector have 2 and 4 parameter sets. The
parameters can be directly addressed via INTERBUS.
They are addressed by means of a code-digit offset:
93XX controllers have 4 parameter sets
(depending on the variant). They are saved
in the EEPROM of the controller.
•
Offset 0 addresses parameter set 1 with the Lenze codes L-C0000
to L-C1999
•
Offset 2000 addresses parameter set 2 with the Lenze codes
L-C2000 to L-C3999
in the EEPROM of the controller.
Another parameter set is in the user
memory of the controller. This parameter
set can be changed by the user.
•
After switch-on parameter set 1 is
No additional
parameter sets available.
•
Offset 4000 addresses parameter set 3
with the Lenze codes L-C4000 to
L-C5999
•
Offset 6000 addresses parameter set 4
with the Lenze codes L-C6000 to
L-C7999
After switch on parameter set 1 is
automatically loaded as current
parameter set.
•
Parameter sets 2 - 4 must be loaded
manually to the RAM.
à
Only the parameter set directly stored in
If a parameter is available only once (see Operating Instructions for
82XX or 8200 vector), use the code digit offset 0.
à
Only the parameter set directly stored in
the RAM can be addressed via
INTERBUS.
Example for L-C0011 (maximum field frequency):
L-C0011 in parameter set 1: Lenze code = 11
L-C0011 in parameter set 2: Lenze code = 2011
-
L-C0011 in parameter set 3:
Lenze code = 4011
L-C0011 in parameter set 4:
Lenze code = 6011
Parameter changes
Automatic saving in the
controller
Automatic saving is default setting
(changeable under L-C0003)
Changes must be stored in code L-C0003.
All changes made without storing them will
be lost after the controller is switched off.
Process data changes
No automatic saving
No automatic saving
No automatic saving
(
(
(
(
Stop!
l
For 8200 vector
– Please observe that cyclic writing of parameter data into the
EEPROM is not permissible.
– Please configure the code to C0003 = 0 after each mains
disconnection if you want to change the parameter data
cyclically.
l
For 82XX
– Please observe that cyclic writing of parameter data into the
EEPROM is not permissible.