2111 interbus fieldbus module, Data transfer drivecom profile parameters – Lenze EMF2111IB User Manual
Page 67
Data transfer
DRIVECOM profile parameters
5
2111 INTERBUS fieldbus module
5.6
5.6.7
L
5.6-45
EDSIBS-1.0-06/2003
This parameter is for the deceleration of the relative speed ramp. The deceleration
time refers to the parameter ” Speed reference value“ .
Ramp gradient:
Gradient =
Speed reference value (604E
hex
)
Deceleration time (6050
hex
)
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
” ramp-min-function” . If the „ deceleration time“ = 0, the ramp is switched off.
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Deceleration time (6050
hex
)
0
S
U32
0 to 495000 [ms]
(max. L-C0013 / 2)
This parameter is assigned to the relative speed ramp for the unit-control
commands ” quick stop” and ” CTRL inhibit” or the QSP terminal function. The
quick stop time refers to the parameter ” Speed reference value“ .
Ramp gradient:
Gradient =
Speed reference value (604E
hex
)
Quich stop time (6051
hex
)
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
” ramp-min-function” . If the ” quick stop time“ = 0, the ramp is switched off.
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Quick-stop time (6051
hex
)
0
S
U32
0 to 495000 [ms]
(max. L-C0105 / 2)
Deceleration time (6050
hex
)
Quick-stop time (6051
hex
)