2111 interbus fieldbus module, Installation electrical installation, Show/hide bookmarks – Lenze EMF2111IB User Manual
Page 12
Installation
Electrical installation
5
2111 INTERBUS fieldbus module
5.4
5.4.3
L
5.4-4
EDSIBS-1.0-06/2003
£
400
m
£ 400 m
3.1
INTERBUS-Loop 100 m
£
£ 10 m
82XX
+
2112
8200 vector
+
2111
93XX
+
2111
82XX
+
2111
93XX
+
2112
8200 vector
+
2112
3.1
3.1
3.2
3.2
3.2
3.2
4.2
4.2
4.2
4.2
2
4
4.1
4.1
4.1
1
3
2111IBU001
Fig. 5.4-2
Wiring example, INTERBUS (baud rate 500 kbit/s)
Pos.
Element
Explanation
1
INTERBUS master with
interface module
The bus system is a master-slave system, i.e. an INTERBUS master is connected
to several field devices (slaves).
2
INTERBUS loop bus
terminal
The bus terminal connects a long distance bus to a peripheral bus.
3
Remote bus
Fig. 5.4-2 Pos. 3
The following connections are possible with remote buses:
•
the INTERBUS master interface module and first bus terminal or first 2111
fieldbus module.
•
the bus terminal and the 2111 fieldbus module
•
two 2111 fieldbus modules
3.1
Long distance bus module Bus participant in the long distance bus; e.g. Lenze controller with INTERBUS
module (slave). Networking does not require bus terminals.
3.2
Remote bus cable
Connects the INTERBUS master interface module with the bus terminal and/or
the long distance bus modules.
4
INTERBUS loop, peripheral
bus
Fig. 5.4-2 Pos. 4
Connection in a peripheral-bus station
A peripheral-bus station consists of:
•
a bus terminal (Fig. 5.4-2 pos. 2)
•
up to eight peripheral bus modules (Fig. 5.4-2 pos. 3)
4.1
INTERBUS loop module
Bus participant in the INTERBUS loop; e.g. Lenze controller with INTERBUS loop
module 2112
4.2
INTERBUS loop cable
Connection within the loop
Features:
Communication medium
RS485
Network topology
Ring
Maximum number of controllers
62
Baud rate / cable length
500 kbit/s / 400 m
Specification of INTERBUS remote bus cable
5
Cable type
Yard goods:
IBS RBC Meter-T, order No. 28 06 28 6 (Fa. Phoenix Contact)
Number of conductors
3 x 2, paired with common shielding
Conductor cross-section
> 0.2 mm
2
DC cable resistance
< 96
Ω/km
Impedance, characteristic
120
Ω ± 20 % (f = 64 kHz)
100
Ω ± 15 Ω (f > 1 MHz)
Capacitance per unit length
< 60 nF/km (f = 800 Hz)
Wiring example