2111 interbus fieldbus module, Show/hide bookmarks – Lenze EMF2111IB User Manual
Page 29

Data transfer
Process data signals of Lenze controllers
5
2111 INTERBUS fieldbus module
5.6
5.6.2
L
5.6-7
EDSIBS-1.0-06/2003
Device status word AIF-STAT for 82XX (Lenze code C0150, index 5F69
hex
)
Bit
820X
821x, 822x
0
Actual parameter set
0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active
Actual parameter set
0 = Parameter set 1 or 3 active
1 = Parameter set 2 or 4 active
1
IMP (pulse inhibit)
0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
IMP (pulse inhibit)
0 = Pulses for power stage enabled
1 = Pulses for power stage inhibited
2
I
max
(current limit reached)
0 = Current limit not reached
1 = Current limit reached
I
max
(current limit reached)
0 = Current limit not reached
1 = Current limit reached
3
not assigned
f
d
= f
dset
0 = f
d
≠ f
dset
1 = f
d
= f
dset
4
f
d
= f
dset
0 = f
d
≠ f
dset
1 = f
d
= f
dset
RFG on = RFG off
0 = RFG on
≠ RFG off
1 = RFG on = RFG out
5
Qmin (f
d
≤ f
dQmin
)
0 = Qmin not active
1 = Qmin active
Qmin (f
d
≤ f
dQmin
)
0 = Qmin not active
1 = Qmin active
6
f
d
+ 0 (act. frequency = 0)
0 = f
d
≠ 0
1 = f
d
+ 0
f
d
+ 0 (act. frequency = 0)
0 = f
d
≠ 0
1 = f
d
+ 0
7
Ctrl. inhibit (controller inhibit)
0 = Controller not inhibited
1 = Controller inhibited
Ctrl. inhibit (controller inhibit)
0 = Controller not inhibited
1 = Controller inhibited
8...11 Controller status
0 = Unit initialisation
8 = Error active
Controller status
0 = Controller initialization
2 = Switch on inhibit
3 = Operation inhibited
4 = Flying-restart circuit active
5 = DC brake active
6 = Operation enabled
7 = Message active
8 = Error active
12
Overtemperature warning
0 = No warning
1 = Warning
Overtemperature warning
0 = No warning
1 = Warning
13
V
Gmax
(DC-bus overvoltage)
0 = No overvoltage
1 = Overvoltage
V
Gmax
(DC-bus overvoltage)
0 = No overvoltage
1 = Overvoltage
14
Direction of rotation
0 = CW rotation
1 = CCW rotation
Direction of rotation
0 = CW rotation
1 = CCW rotation
15
Ready for operation
0 = Not ready for operation
1 = Ready for operation
Ready for operation
0 = Not ready for operation
1 = Ready for operation
16 bits
16 bits
.B15
.B12
.B0
.B1
.B2
.B3
.B4
.B8
.B9
.B10
.B11
.B13
.B14
.B5
.B6
.B7
IMP
fd=fdset / RFG
Qmin
Imax
- / fd=fdset
PAR
fd>0
ctrl. inhibit
Vgmax
R/L
RDY
T ü
AIF
C0050
STAT
B11 B10 B9 B8
0
0
1...
...
0
1
1...
...
0
0
0...
...
0
0
0...
...
0
2
3...
...
2141LON012_en
Fig. 5.6-1
Read access to status word and actual frequency in 82XX (fixed assignment)
Show/Hide Bookmarks