2111 interbus fieldbus module, Data transfer drivecom profile parameters – Lenze EMF2111IB User Manual
Page 64
Data transfer
DRIVECOM profile parameters
5
2111 INTERBUS fieldbus module
5.6
5.6.7
L
5.6-42
EDSIBS-1.0-06/2003
The parameter indicates the pole number of asynchronous motors and is used to
convert frequency values into speed values. Only even values are possible.
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Pole number (604D
hex
)
0
S
U8
2, 4, 6, ..., 254
Lenze setting:
4
This parameter is the reference value for the relative speed parameters, e.g.
nominal percentage, actual percentage and acceleration time. The parameter is
mapped to the Lenze parameter L-C0011. A conversion to frequency values is
possible. The parameter determines the internal maximum speed, which is also
active with terminal control.
Parameter name (Index)
Subindex
Data structure
Data type
Meaning
Speed reference value (604E
hex
)
0
S
U32
L-C0011
2
in [rev∕min]
This parameter is the nominal speed in percent. It is scaled to the ” speed
reference value“ (= 100 % ). When changing this parameter, also the ” nominal
speed“ will be changed. If the ” nominal speed“ exceeds the limit value of the
” nominal percentage“ of 200 % during reading, it will be returned as a value
limited to 200 % .
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Percentage setpoint (6052
hex
)
0
S
I16
−32768 to 32767
(100 % = 16383)
This parameter is the ” speed reference variable“ in percent. It is scaled to the
” speed reference value“ (= 100 % ). The ” percentage reference variable“ is
multiplied by the inverse ” setpoint factor“ .
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Percentage reference variable
(6053
hex
)
0
S
I16
−32768 to 32767
(100 % = 16383)
This parameter is the ” actual speed“ in percent. It is scaled to the ” speed
reference value“ .
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Actual percentage (6054
hex
)
0
S
I16
−32768 to 32767
(100 % = 16383)
Map of L-C0381
Pole number (604D
hex
)
13
Speed reference value (604E
hex
)
Percentage setpoint (6052
hex
)
14
Percentage reference variable
(6053
hex
)
Actual percentage (6054
hex
)
15
Show/Hide Bookmarks