2111 interbus fieldbus module, 3 technical data, 1 general data and application conditions – Lenze EMF2111IB User Manual
Page 5: 2 rated data, 3 protocol data
Technical data
General data and application conditions
5
2111 INTERBUS fieldbus module
5.3
5.3.1
L
5.3-1
EDSIBS-1.0-06/2003
5.3
Technical data
5.3.1
General data and application conditions
Field
Values
Order number
EMF 2111IB
Communication media
RS485
Network topology
Ring
INTERBUS participant
Slave
Communication profile
PCP 1.5
Drive profile
DRIVECOM profile 21
Baud rate
500 kBit/s
Baud rate
500 kBit/s
Ambient temperature
during operation:
during transport:
during storage
0
°C
-25
°C
-25
°C
to
to
to
55 °C
70 °C
60 °C
Permissible humidity
Class 3K3 to EN 50178
(without condensation, average relative humidity 85%)
Degree of pollution
VDE0110, part 2, pollution degree 2
Enclosure
IP 20
Voltage supply (internal / external),
see
^ 5.4-5
External supply via separate power supply unit
(+24 V DC ±10 %, max. 150 mA)
5.3.2
Rated data
Insulation voltage between bus and ...
Rated insulation voltage
Type of insulation
•
Earth reference / PE
50 V AC
Mains isolation
•
External supply (terminal 39/59)
0 V AC
No mains isolation
•
Power stage
– 820X / 821X
270 V AC
Basic insulation
– 822X / 8200 vector
270 V AC
Double insulation
– 93XX
270 V AC
Double insulation
•
Control terminals
– 820X / 8200 vector
(with internal supply)
0 V AC
No mains isolation
– 8200 vector
(with external supply)
100 V AC
Basic insulation
– 821X
50 V AC
Mains isolation
– 822X
270 V AC
Basic insulation
– 93XX
270 V AC
Basic insulation
5.3.3
Protocol data
Field
Values
Maximum number of participants
62
Process data words (PD)
L-C1910 = 4: 2 words (32 bit)
L-C1910 = 6: 3 words (48 bit)
à
Lenze setting
Parameter data words (PCP)
1 (16 bit)
Maximum number of data words
The maximum number of data words (PD + PCP) is 4.
INTERBUS ID (module ID)
227
dec
= E3
hex
PCP 1 word
Maximum PDU length
64 byte
Supported PCP services
Initiate, abort, status, identify, Get-0V-long, read, write