Data transfer
DRIVECOM profile parameters
5
2111 INTERBUS fieldbus module
5.6
5.6.7
L
5.6-36
EDSIBS-1.0-06/2003
Bit
Name
Meaning
0
Switch on
Controller status
0 = command 2, 6, 8 (controller inhibit)
1 = command 3 (controller inhibit)
1
Voltage inhibit
Controller status
0 = command 9, 10, 12 (controller inhibit)
1 = command ”voltage inhibit“ not active
2
Quick stop
Controller status
0 = Command 7, 10, 11 (quick stop)
1 = Command ”quick stop“ not active
3
Operation
enable
Controller status
0 = Command 5 (controller inhibit)
1 = Command 4 (controller inhibit not active)
4
RFG inhibit
Inhibit of the
ramp-funtion
generator.
Quick stop is activated without the controller leaving its status.
0 = RFG inhibit (quick stop)
1 = RFG inhibit not active
5
FREE
820X:
Not assigned
5
FREE
DRIVECOM:
RFG-stop
821X, 822X:
Output of the RFG (speed setpoint integrator) is ”frozen”.
0 = RFG stop
1 = RFG stop not active
RFG stop
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B4 negated.
6
FREE
820X:
Not assigned
6
FREE
DRIVECOM:
RFG-zero
821X, 822X:
Ramp function generator input (speed setpoint integrator) = 0
(controlled deceleration along the set ramp)
0 = RFG zero
1 = RFG zero not active
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B5 negated.
7
Error reset
Fault reset (TRIP). For this, a bit change from 0 to 1 is required.
For 82XX, the controller is initialised. During this time, the controller does not accept any
commands.
8 - 10 Reserve
DRIVECOM reserved
11
FREE
DRIVECOM:
820X, 821X, 822X:
Not assigned
DRIVECOM:
Manufacturer
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B7.
12
FREE
DRIVECOM:
Manufacturer
820X, 821X, 822X:
Parameter set changeover:
0
® 1 = Parameter set 2
1
® 0 = Parameter set 1
Manufacturer
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B12.
13
FREE
DRIVECOM:
Manufacturer
820X, 821X, 822X:
DC-injection brake:
0 = DCB not active
1 = DCB active
Manufacturer
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B13.
14
FREE
DRIVECOM:
820X, 821X, 822X:
Not assigned
DRIVECOM:
Manufacturer
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B14.
15
FREE
DRIVECOM:
Manufacturer
8201X
PE inhibit
Inhibit the update of the PO data of the controller (input data for
the master).
Updates of status and current information of the process channel
can be inhibited in order to send control information more
precisely in time (see chapter 5.3.4.2).
0 = Read status and actual value
1 = Do not read status and actual value
821X, 822X:
Not assigned
8200 vector, 93XX:
Free. Mapping to bit AIF-CTRL.B15.
Structure of the DRIVECOM
control word