2111 interbus fieldbus module – Lenze EMF2111IB User Manual
Page 46
Data transfer
Process data preconfiguration depending on L-C0009
5
2111 INTERBUS fieldbus module
5.6
5.6.3
L
5.6-24
EDSIBS-1.0-06/2003
Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures
1. Remove the fieldbus module and disconnect it from the voltage
supply
2 Set L-C0009 = 14 (e g via keypad)
2. Set L-C0009 = 14 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage
supply
Result
•
The indexes 6000
hex
and 6001
hex
accept the configurations DCSTW
and DCG.
•
The process data length (PD) is set to 2 words by L-C1910 = 4.
•
DRIVECOM is activated with L-C1911 = 1.
Acceptance of settings
The fieldbus module must be switched on again to activate the process
data word length.
Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures
1. Remove the fieldbus module and disconnect it from the voltage
supply
2. Set L-C0009 = 25 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage
supply
Result
•
The indexes 6000
hex
and 6001
hex
accept the configurations GSTW,
AIF-W1, AIF-W2.
•
The process data length (PD) is set to 3 words by L-C1910 = 6.
•
DRIVECOM is activated by L-C1911 = 0.
Acceptance of settings
The fieldbus module must be switched on again to activate the process
data word length.
Examples for process data
preconfiguration