Data transfer
DRIVECOM profile parameters
5
2111 INTERBUS fieldbus module
5.6
5.6.7
L
5.6-44
EDSIBS-1.0-06/2003
This parameter contains data of the absolute speed ramp for deceleration.
Ramp gradient:
Gradient =
Delta_speed
Delta_time
The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
” ramp-min-function” . If the ” delta_time“ = 0, the ramp is switched off.
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Speed delay (6049
hex
)
1
RS (21
hex
)
U32
0 to 4294967295
0: Delta_speed [rev/min]
2
RS (21
hex
)
U16
0 to 65535
0 (ramp is switched off):
Delta_time [sec]
This parameter contains the data of the absolute speed ramp for deceleration in
the status ” QUICKSTOP“ or ” CTRL INHIBIT“ or the QSP terminal function.
Ramp gradient:
Gradient =
Delta_speed
Delta_time
The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
” ramp-min-function” . If the ” delta_time“ = 0, the ramp is switched off.
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Quick stop
(604A
hex
)
1
RS (21
hex
)
U32
0 to 4294967295
0: Delta_speed [rev/min]
2
RS (21
hex
)
U16
0 to 65535
0 (ramp is switched off):
Delta_time [sec]
This parameter is for the acceleration of the relative speed ramp. The acceleration
time refers to the parameter ” speed reference” with the following slope:
Ramp gradient:
Gradient =
Speed reference value (604E
hex
)
Acceleration time (604F
hex
)
The parameter is mapped to the Lenze acceleration ramp (L-C0012) via the
” ramp-min-function” . If the ” acceleration time“ = 0, the ramp is switched off.
Parameter name (Index)
Subindex
Data structure
Data type
Value range
Acceleration time (604F
hex
)
0
S
U32
0 to 495000 [ms]
(max. L-C0012 / 2)
Speed ramps for deceleration
(6049
hex
)
Speed quick stop (604A
hex
)
Acceleration time (604F
hex
)