Commissioning
Start up of the 2111 fieldbus module
5
2111 INTERBUS fieldbus module
5.5
5.5.3
L
5.5-2
EDSIBS-1.0-06/2003
If you do not use the program ” SYSSWT” , the following settings must be made:
Name
Entry
Explanation
Module/PD length
2
2
3
Process-data length in words (16 bit each)
for 82XX
for 93XX Lenze setting (L-C1910 = 4)
for 93XX, when code L-C1910 = 6
Module ID
227
Module identification
Tab. 5.5-1
Process-data communication
Name
Entry
Explanation
COM_REF
2 or higher
Communication reference (CR)
CONN_TYPE
Acyclic
master/slave
Connection type
CONN_ATTR
Defined
Connection attribute
Max PDU sending high prio
0
Sending history high priority
Max PDU sending low prio
64
Sending history low priority
Max PDU receiving high prio
0
Receiving history high priority
Max PDU receiving low prio
64
Receiving history low priority
Supported service request
803000
hex
Supported service, master request
Supported Services Response
000000
hex
Supported service, slave response
Maximum SCC
1
Maximum RCC
0
Maximum SAC
0
Maximum RAC
0
Tab. 5.5-2
PCP communication
5.5.3
Start up of the 2111 fieldbus module
1. The fieldbus module must be attached to the controller
(
¶ 5.4-2)
.
2. Switch on the controller and, if required, the external voltage supply of the
2111 fieldbus module.
3. Check fieldbus module signals:
– The green bus LED indicates the operating status according to the
corresponding description
(
¶ 5.4-1)
Pos.
0.
– The yellow bus LED indicates the communication status according to the
description
(
¶ 5.4-1)
Pos.
1.
– If the signals are different in any way please see the chapter
“ Troubleshooting and fault elimination” .
4. You can now communicate with the drive.
– With a PCP communication it is only possible to access the parameters of
the controller after having executed the PCP service ” Initiate“
(
¶ 5.6-49)
.
5. It is then possible to access the parameters via the PCP services ” Read“
and ” Write“
(
¶ 5.6-49)
.
Different program